240V domestic supplies in shared multimeter buildings 1 shot 10/350 Iimp 2KA
Data sheet – Protec CM 80/275
- 1 shot 10/350 Iimp 2KA /pole used in multi metered developments such as multi storey flats and student accommodation where the structured mains supply is the utility company property
- Category IEC / EN / VDE: Class II / Type 2 / C
- Location of use: Sub-distribution boards
- Network system: TN-S
- Protection modes: L/N – PE, L- N
- Protective element: MOV and GDT
- Surge discharge rating: Imax = 20kA Iimp =2KA
- Housing: Modular design
- Complies with: IEC/EN 61643-11
- Minimum 12 units to be installed in parallel on network mains to comply with BSEN 62305 design when calculating current division